Model | SRM6-125HL | SRM6-160HL | SRM6-250HL | SRM6-320HL | SRM6-400HL | SRM6-630HL |
Frame grade current Inm (A) | 125 | 160 | 250 | 320 | 400 | 630 |
Number of poles | 3,4 | |||||
Rated operating voltage Ue | AC400V/415V/690V | |||||
Rated insulation voltage Ui (V) | AC800 | AC1000 | ||||
Rated impact voltage Uimp (kV) | 8 | 12 | ||||
Rated current (A) | 32, 40, 50, 63, 80, 100, 125 | 140, 160 | 125, 140, 160, 180, 200, 225, 250 | 280, 315, 320 | 225, 250, 315, 350, 400 | 500, 630 |
Type of overcurrent release device | Thermomagnetic type | |||||
Ultimate short-circuit breaking capacity Icu (kA)AC415V | 50 | 70 | ||||
Operating short circuit breaking capacity Ics (kA)AC415V | 35 | 50 | ||||
Category of use | A | |||||
Whether it has the isolation function | Yes | |||||
Operating ambient temperature | -35ºC~+70ºC | |||||
Arc distance (mm) | 0 | |||||
Mechanical life (no maintenance)(times) | 20000 | 10000 | ||||
Electrical life | 8000 | 5000 - |
||||
Meet standard | IEC/EN 60947-2, GB/T 14048.2 | |||||
Authentication | CCC, CB, CE, TUV | |||||
Outline dimensions (L×W×H)(mm) | 213×92×159(3P) | 227×107×159(3P) | 324×150×159(3P) | |||
213×122×159(4P) | 227×142×159(4P) | 324×198×159(4P) |
Model | SRM6DC - 125HL | SRM6DC - 160HL | SRM6DC - 250HL | SRM6DC - 320HL | SRM6DC - 400HL | SRM6DC - 630HL |
Frame grade current Inm (A) | 125 | 160 | 250 | 320 | 400 | 630 |
Number of poles | 3, 4 | |||||
Rated operating voltage Ue (V) | DC1000V/1250V/1500V | |||||
Rated insulation voltage Ui (V) | DC1500V | |||||
Rated impact voltage Uimp (kV) | 8 | 12 | ||||
Rated current In (A) | 32, 40, 50, 63, 80, 100, 125 | 140, 160 | 125, 140, 160, 180, 200, 225, 250 | 280, 315, 320 | 225, 250, 315, 350, 400 | 500, 630 |
Type of overcurrent release device | Thermomagnetic type | |||||
Ultimate short - circuit breaking capacity Icu (kA) DC1000/1250/1500V | 10 | |||||
Operating short Circuit breaking capability Ics (kA) DC1000/1250/1500V | Ics = 100%Icu | |||||
Category of use | A | |||||
Whether it has the isolation function | Yes | |||||
Operating ambient temperature | -35ºC~ + 70ºC | |||||
Arc distance (mm) | 0 | |||||
Mechanical life (nomaintenance)(times) | 8500 | 7000 | ||||
Electrical life | 1500 | 1000 | ||||
Meet standard | IEC/EN 60947 - 2, GB/T 14048.2 | |||||
Authentication | CCC, CB, CE, TUV | |||||
Outline dimensions (L×W×H)(mm) | 213×92×159(3P) | 227×107×159(3P) | 324×150×159(3P) | |||
213×122×159(4P) | 227×142×159(4P) | 324×198×159(4P) |
Model | SRM6E-125HL | SRM6E - 160HL | SRM6E - 250HL | SRM6E - 320HL | SRM6E - 400HL | SRM6E - 630HL |
Frame grade current Inm (A) | 125 | 160 | 250 | 320 | 400 | 630 |
Number of poles | 3, 4 | |||||
Rated operating voltage Ue (V) | AC400V/415V/690V | |||||
Rated insulation voltage Ui (V) | AC800 | AC1000 | ||||
Rated impact voltage Uimp (kV) | 8 | 12 | ||||
Rated current In (A) | 40, 100, 125 | 140, 160 | 160, 250 | 320 | 300, 350, 400 | 500, 630 |
Type of overcurrent release device | Electronic release device | |||||
Overload long delay release setting current IR | (0.4-0.5-0.6-0.7-0.8-0.9-1)In | |||||
Short - circuit short - delay release setting current Isd | (1.5-2-3-4-5-6-8)IR+OFF | |||||
Short circuit instantaneous release setting current Ii | (2-3-4-6-8-10-12)In+OFF | |||||
Neutral pole protects Im | (0.5, 1) In+OFF, adjustable | |||||
Short - circuit short delay setting time tsd | (0.06s, 0.1s, 0.2s, 0.3s)+OFF | |||||
Overload long delay release time tR | 12s, 60s, 80s, 100s, 150s | |||||
Ultimate short - circuit breaking capacity Icu (kA)AC415V | 50 | 70 | ||||
Operating short circuit breaking capability Ics (kA)AC415V | 35 | 50 | ||||
Category of use | A | |||||
Whether it has the isolation function | Yes | |||||
Operating ambient temperature | -35ºC~+70ºC(Knob type), -20ºC~+70ºC(LCD type) | |||||
Arc distance (mm) | 0 | |||||
Mechanical life (no maintenance)(times) | 20000 | 10000 | ||||
Electrical life | 8000 | 5000 | ||||
Meet standard | IEC/EN 60947-2, GB/T 14048.2 | |||||
Authentication | CCC, CB, CE, TUV | |||||
Outline dimensions (L×W×H)(mm) | 213×92×159(3P) | 227×107×159(3P) | 324×150×159(3P) | |||
213×122×159(4P) | 227×142×159(4P) | 324×198×159(4P) |